![]() |
||||||||||
|
|
|
|||||||||
|
|
A ROUGH GUIDE TO FIRE DETECTION AND ALARM SYSTEMS
Systems designed to protect life are know as Category L. Some smaller buildings may not have or need an FD+a system, for example a small open plan area where someone shouting “fire” can be heard all around. Non–Addressable The basic technology is Non–Addressable which is found more often in smaller buildings due to it being more cost effective. A non-addressable system is simply comprised of Fire zones. These are represented by red l.e.d.s on the control panel. Faults use amber l.e.d.s. A zone is how a building is split up to speed the location of a fire. For example if a building was not zoned then in the case of a fire, the whole building would have to be searched instead of being directed to the exact zone area by the control panel. This would dramatically slow up the location process and would result in more damage and possibly loss of life. Each zone is made up of a grouping of AFD and MCP’s and in the event of a fire being detected either automatically by AFD of manually by a person discovering a fire and operating the MCP,will cause the control panel to enter fire condition which will then operate the alarm sounders thus alerting the occupants. The Zone in fire condition would then have to be checked to establish the exact detector that caused the alarm. If an AFD was the cause a red l.e.d would be illuminated on the detector itself. The zone wiring is in a redial circuit and terminated with an end of line device or resistor which enables the panel to monitor the wiring for short and open circuit faults. The panel will typically have two on board alarm sounder circuits which in normal operation send a reversed voltage down each circuit to monitor for faults. The voltage is reversed otherwise the sounders would be on constantly but is changed to normal polarity in a fire condition. The panel requires a dedicated 240v ac supply and where it is then reduced down through a transformer and then changed to its operating voltage of 24 volts DC via a bridge rectifier. The batteries in the fire panel should be replaced at least every 4 years or when testing dictates. In this system the physical wiring dictates the zoning and the detector decides if it’s a fire condition or not. Analogue Addressable: The second technology is far more advanced and is normally found in the larger premises. This is called Analogue Addressable and will pin point the exact location of a fire through zoning and also the detector in fire having it’s own number (address) and text allocated to it.
This system is wired in a loop and unlike the non addressable the zoning is done through programming, so the same cable can pass through the whole building. A typical loop can have up to 126 devices which are constantly tested by the control panel. On this system should a part of the loop wiring become damaged short circuit isolators ( SCI ) either side of the fault will shut down that particular section of wiring and continue to operate with the reminder of the wiring and devices. Again unlike the non addressable which would loose the zone in fault. When a detector on the loop senses a fire, information is passed back to the control panel which is then processed and a decision is made by the panel not the detector whether it is a fire or not. Unlike the non addressable system each detector or MCP reports it analogue value back to the control panels front end processor ( FEP ). The device reports back whether it’s in a pre-alarm, alarm or fault state by differing analogue values. Under normal conditions the levels are low but if smoke enters the detector chamber the level will rise until it reaches a predetermined threshold and enters fire condition. Individual detectors can have their threshold levels altered so for example can be less sensitive during the day and more at night if required. Another advantage it has over non addressable technology is that individual detectors can be isolated instead or an entire zone. This system can dramatically reduce unwanted alarms and unlike non addressable will let the user aware if a detector has become faulty. In the event of a fire or fault the control panel offers text description of the condition, unlike the non addressable which will only illuminate relevant led’s. This make the location of fire and faults much quicker. The panel operates on the same voltage as the non addressable and also has battery back up. As with both non addressable and addressable all wiring must be in fire resistant cable. There is also wire free radio based analogue addressable fire systems which have all the benefits of a hard wire system but with the obvious advantage of no cabling required to all the devices. This is an ideal option for listed buildings such as Churches, where cable runs would look unsightly. There is also no damage to the building or mess from drilling. Installation is far quicker and far less labour intensive but has the drawback of having to replace every battery in each device approximately every 5 years. The equipment is more expensive than hard wired but on the larger installations the reduction in labour costs can be balanced against the cost of hardwired. Both addressable and non addressable use devices which are designed to detect fires and give audible warning. These are:
Smoke detectors: The smoke detector has a few variations such as Optical, ionization, aspirating smoke detector ( ASD ) and modern combined smoke and heat. Optical is the most widely used and is more suited to detecting a slow burning fire which gives off larger smoke particles. Ionisation which are beginning to be phased out detect a quick burning fire which generates more heat and thinner smoke particles. The Aspirating smoke detector draws air from an area via a network of pipes which have sampling holes. The ASD can detect very small amounts of smoke and has a high sensitivity. The smoke is drawn through the holes in the pipes and back to a central aspirating detector. This is a common choice for areas such as computer suites, telecommunication room’s etc where the earliest possible warning of a fire is crucial to protect such sensitive equipment. The manual Call point: The red box on the wall that everyone is familiar with. In the event of a fire a person would break the glass in the unit which in turn activates the fire alarm. Most commonly found at all exits to the outside of a building. Heat Detector: Comes in two variants and are most commonly found in kitchens, boiler rooms or un clean environments. They come as Rate of Rise which detects a rapid increase in temperature or fixed temperature which will only activate after the room temperature exceeds a pre determined temperature set into the detector. The alarm sounder: Normally red and alerts occupants audibly to a fire. These can be supplemented by visual alarms ( flashing beacons ) where areas can be normally noisy i.e. factories or DDA compliance. General sound level required is 65 DBa or 75 DBa in a room of sleep at bed head level. Beam Detector: Normally used in large areas such as warehouses. The beam detector can emit a beam reaching up to 100m in length from one end of a building to the other and can cover 1500m2 with a single unit. The beam is optical and when obscured by smoke ( obscuration ) will activate the fire alarm. All fire systems must be regularly tested and maintenance is essential as it will prolong the life of a system and discover any faults that may occur. Feature contributed by Graeme Miller. |
|||||||||
|
|